GROUP PDF |
GEN ET-300T SERIES, WITH
IGBT RECTIFIER, OUTPUT ISOLATION TRANSFORMER, 10- 400kVA |
UPS |
BATTERY OPTIONS |
TIME |
Model |
Power |
Battery
Qty |
Battery |
Battery
Cabinet |
Battery
Cable Breaker |
Time (Minutes) |
|
GEN ET-3120T |
120kVA |
104 |
12V 24AH |
2 x BC01MP-2K |
OPT |
7 / 19 |
|
52 |
12V
70AH |
2 x BC01MP-2K |
OPT |
9 / 27 |
|
52 |
12V 80AH |
2 x BC01MP-2K |
OPT |
14 / 31 |
|
52 |
12V 105AH |
2 x BC01MP-2K |
OPT |
22 / 48 |
|
156 |
12V 40AH |
3 x BC01MP-2K |
OPT |
27 / 58 |
|
104 |
12V 70AH |
4 x BC01MP-2K |
OPT |
29 / 66 |
|
104 |
12V 80AH |
4 x BC01MP-2K |
OPT |
31 / 70 |
|
104 |
12V 105AH |
4 x BC01MP-2K |
OPT |
48 / 108 |
|
Model |
Power |
Battery
Qty |
Battery |
Battery
Cabinet |
Battery
Cable Breaker |
Time (Minutes) |
|
GEN ET-3160T |
160kVA |
52 |
12V 70AH |
2 x BC01MP-2K |
OPT |
4 / 15 |
|
52 |
12V
80AH |
2 x BC01MP-2K |
OPT |
5 / 22 |
|
52 |
12V 105AH |
2 x BC01MP-2K |
OPT |
15 / 34 |
|
104 |
12V 70AH |
4 x BC01MP-2K |
OPT |
18 / 47 |
|
104 |
12V 80AH |
4 x BC01MP-2K |
OPT |
23 / 50 |
|
104 |
12V 105AH |
4 x BC01MP-2K |
OPT |
34 / 78 |
|
156 |
12V 80AH |
6 x BC01MP-2K |
OPT |
37 / 84 |
|
Model |
Power |
Battery
Qty |
Battery |
Battery
Cabinet |
Battery
Cable Breaker |
Time (Minutes) |
|
GEN ET-3200T |
200kVA |
52 |
12V 80AH |
2 x BC01MP-2K |
OPT |
4 / 16 |
|
52 |
12V 105AH |
2 x BC01MP-2K |
OPT |
9 / 27 |
|
104 |
12V 70AH |
4 x BC01MP-2K |
OPT |
10 / 37 |
|
104 |
12V 80AH |
4 x BC01MP-2K |
OPT |
17 / 40 |
|
104 |
12V 105AH |
4 x BC01MP-2K |
OPT |
27 / 59 |
|
156 |
12V 80AH |
6 x BC01MP-2K |
OPT |
28 / 63 |
|
156 |
12V 105AH |
6 x BC01MP-2K |
OPT |
43 / 93 |
|
Model |
Power |
Battery
Qty |
Battery |
Battery
Cabinet |
Battery
Cable Breaker |
Time (Minutes) |
|
GEN ET-3250T |
250kVA |
52 |
12V 105AH |
2 x BC01MP-2K |
OPT |
5 / 21 |
|
104 |
12V
70AH |
4 x BC01MP-2K |
OPT |
6 / 26 |
|
104 |
12V 80AH |
4 x BC01MP-2K |
OPT |
10 / 30 |
|
104 |
12V 105AH |
4 x BC01MP-2K |
OPT |
20 / 46 |
|
156 |
12V 80AH |
6 x BC01MP-2K |
OPT |
22 / 50 |
|
156 |
12V 105AH |
6 x BC01MP-2K |
OPT |
33 / 74 |
|
Model |
Power |
Battery
Qty |
Battery |
Battery
Cabinet |
Battery
Cable Breaker |
Time (Minutes) |
|
GEN ET-3300T |
300kVA |
104 |
12V 70AH |
4 x BC01MP-2K |
OPT |
5 / 19 |
|
104 |
12V
80AH |
4 x BC01MP-2K |
OPT |
6 / 24 |
|
104 |
12V 105AH |
4 x BC01MP-2K |
OPT |
16 / 38 |
|
156 |
12V 70AH |
6 x BC01MP-2K |
OPT |
12 / 35 |
|
156 |
12V 80AH |
6 x BC01MP-2K |
OPT |
17 / 40 |
|
156 |
12V 105AH |
6 x BC01MP-2K |
OPT |
27 / 59 |
|
Model |
Power |
Battery
Qty |
Battery |
Battery
Cabinet |
Battery
Cable Breaker |
Time (Minutes) |
|
GEN ET-3400T |
400kVA |
104 |
12V 105AH |
4 x BC01MP-2K |
OPT |
9 / 27 |
|
156 |
12V
70AH |
6 x BC01MP-2K |
OPT |
5 / 24 |
|
156 |
12V 80AH |
6 x BC01MP-2K |
OPT |
10 / 27 |
|
156 |
12V 105AH |
6 x BC01MP-2K |
OPT |
20 / 43 |
|
|
|
|
|
|
|
|
|
|
|
* Battery duration are
calculated as %100 and %50 loads. |
|
|
|
* Battery duration are
calculated under 0,7 Pf. |
|
|
|
* Generg will supply
min. 10 years spare parts for the products. |
|
|
|
* Warranty is 2 years
for manufacturer defects. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|