GROUP PDF |
GEN ET200 SERIE 10-20kVA
WITH IGBT RECTIFIER |
UPS |
BATTERY OPTIONS |
TIME |
Model |
Power |
Battery
Qty |
Battery |
Battery
Cabinet |
Battery
Cable Breaker |
Time (Minutes) |
|
GEN ET-210SH |
10kVA |
60 |
12V 4,5AH |
BCS6405 |
Included |
6 / 19 |
|
60 |
12V 7AH |
BCS6607 |
Included |
15 / 47 |
|
60 |
12V 9AH |
BCS6607 |
Included |
23 / 56 |
|
60 |
12V 12AH |
BC40 |
OPT |
30 / 72 |
|
120 |
12V 7AH |
BC40 |
OPT |
47 / 109 |
|
120 |
12V 9AH |
BC40 |
OPT |
56 / 123 |
|
Model |
Power |
Battery
Qty |
Battery |
Battery
Cabinet |
Battery
Cable Breaker |
Time (Minutes) |
|
GEN ET-215SH |
15kVA |
60 |
12V
4,5AH |
BCS6405 |
Included |
4 / 10 |
|
60 |
12V 7AH |
BCS6607 |
Included |
6 / 29 |
|
60 |
12V 9AH |
BCS6607 |
Included |
14 / 34 |
|
60 |
12V 12AH |
BC40 |
OPT |
17 / 48 |
|
120 |
12V 7AH |
BC40 |
OPT |
29 / 66 |
|
120 |
12V 9AH |
BC40 |
OPT |
34 / 75 |
|
60 |
12V 24AH |
BC01MP-2K |
OPT |
51 / 123 |
|
Model |
Power |
Battery
Qty |
Battery |
Battery
Cabinet |
Battery
Cable Breaker |
Time (Minutes) |
|
GEN ET-220SH |
20kVA |
60 |
12V
4,5AH |
BCS6405 |
$0 |
3 / 6 |
|
60 |
12V 7AH |
BCS6607 |
$0 |
4 / 15 |
|
60 |
12V 9AH |
BCS6607 |
$0 |
9 / 23 |
|
120 |
12V 7AH |
BC40 |
OPT |
15 / 47 |
|
120 |
12V 9AH |
BC40 |
OPT |
23 / 56 |
|
60 |
12V 24AH |
BC01MP-2K |
OPT |
38 / 81 |
|
120 |
12V 18AH |
BC01MP-2K |
OPT |
62 / 155 |
|
60 |
12V 40AH |
BC01MP-2K |
OPT |
68 / 164 |
|
|
|
|
|
|
|
|
|
|
|
* ET-200 series are
special and customized serie manufactured only after order confirmation. So
there is no technical datasheet. |
|
|
* Battery duration are
calculated as %100 and %50 loads. |
|
|
|
* Battery duration are
calculated under 0,7 Pf. |
|
|
|
* Generg will supply
min. 10 years spare parts for the products. |
|
|
|
* Warranty is 2 years
for manufacturer defects. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|